1、附表2.1 酒店變配電房1,HT1、HT2負荷計算表序 用電設(shè)備組名稱數(shù)量/面積單位容量額定容量需用系數(shù)功率因數(shù)計算負荷號nkW/nkWKxCOSPjs(kW)Qjs(kvar)Sjs(kVA)一、酒店客房1標(biāo)準間1203.5420.00.500.85210.00130.10247.032大床房1203.5420.00.500.85210.00130.10247.033套房1205600.00.500.85300.00185.90352.93二、公共設(shè)施4客房層照明/小動力85000.02170.00.800.85136.0084.30160.0151F酒店大堂10800.0443.20.80
2、0.8534.6021.4040.686避難層34700.0134.70.800.8527.8017.2032.697全日餐廳預(yù)留1001100.00.800.8580.0049.6094.138B1層后勤區(qū)47000.03141.00.500.8570.5043.7082.959預(yù)留泛光照明1100100.00.500.8550.0031.0058.8310預(yù)留廣告及LED屏照明1100100.00.500.8550.0031.0058.8311預(yù)留園林用電16060.00.800.8548.0029.7056.45三、動力設(shè)備12垂直電梯24386.00.400.6034.4045.905
3、7.3613垂直電梯434136.00.900.85122.4075.90144.0214變配電房22040.00.900.8536.0022.3042.3515弱電機房16060.00.800.8548.0029.7056.4516衛(wèi)星電視機房15050.00.900.8545.0027.9052.9517消防控制中心18080.00.700.8056.0042.0070.0018鍋爐房14545.00.400.8018.0013.5022.5019廚房預(yù)留1500500.00.700.80350.00262.50437.5020防排煙設(shè)備(最大組合)1300300.00.700.80210
4、.00157.50262.5021空調(diào)末端1600600.00.700.80420.00315.00525.0022消火栓接力泵275150.00.000.800.000.000.0023噴淋接力泵19090.00.000.800.000.000.0024酒店變頻調(diào)速供水設(shè)備110.210.20.800.808.206.2010.2825生活水泵196.596.50.600.8057.9043.4072.3626航空障礙燈11010.00.800.808.006.0010.0027低壓側(cè)合計4442.602630.801801.803188.6728乘以同時系數(shù)0.902367.721621.
5、622869.8029自然功率因素cos0.8230自動補償(kVar)(844.00)31總安裝補償容量(kVar)(960.00)32補償后0.952367.72777.622492.1533變壓器容量(kVA)2x1600(kVA)3200.0034變壓器負荷率0.7735變壓器損耗24.92124.6136變壓器高壓側(cè)計算負荷2392.64902.232557.10附表2.2 酒店變配電房1,HT3、HT4負荷計算表序 用電設(shè)備組名稱數(shù)量/面積單位容量額定容量需用系數(shù)功率因數(shù)計算負荷號nkW/nkWKxCOSPjs(kW)Qjs(kvar)Sjs(kVA)四、空調(diào)制冷設(shè)備1酒店冷卻塔2
6、1530.00.800.8024.0018.0030.002冷水機組26201240.00.800.80992.00744.001240.003冷水機組1316316.00.000.800.000.000.004冷卻水泵275150.00.800.80120.0090.00150.005冷凍水泵275150.00.800.80120.0090.00150.006熱回收循環(huán)泵11.51.50.800.801.200.901.507熱水鍋爐循環(huán)泵23060.00.800.8048.0036.0060.008中餐廳38250.05191.250.800.85153.0094.80179.999多功能
7、廳6090.0530.450.800.8524.4015.1028.6910宴會廳、會議室及前廳52830.1528.300.800.85422.60261.90497.1711廚房預(yù)留1800800.000.400.80320.00240.00400.0012垂直電梯622132.000.400.6052.8070.4088.0013自動扶梯31545.000.700.8031.5023.6039.3614低壓側(cè)合計3674.502309.501684.702858.6715乘以同時系數(shù)1.002309.501684.702858.6716自然功率因素cos0.8017自動補償(kVar)(
8、926.00)18總安裝補償容量(kVar)(600.00)19補償后0.952309.50758.702430.9320變壓器容量(kVA)2x1600(kVA)3200.0021變壓器負荷率0.7622變壓器損耗24.31121.5523變壓器高壓側(cè)計算負荷2333.81880.252494.29附表2.3 1#樓辦公變配電房1,OT1、OT2負荷計算表序 用電設(shè)備組名稱數(shù)量/面積單位容量額定容量需用系數(shù)功率因數(shù)計算負荷號nkW/nkWKxCOSPjs(kW)Qjs(kvar)Sjs(kVA)一、商務(wù)辦公1辦公(未包括中央空調(diào)主機)253800.082030.400.700.801421.
9、301066.001776.64二、公共設(shè)施2辦公公共區(qū)域93200.02186.400.700.80130.5097.90163.14338F避難層/航空障礙燈17350.0234.700.800.8527.8017.2032.694預(yù)留泛光照明1100100.000.500.8550.0031.0058.835預(yù)留廣告及LED屏照明1100100.000.600.8560.0037.2070.60三、動力設(shè)備6垂直電梯661366.000.400.60146.40195.20244.007垂直電梯24386.000.400.6034.4045.9057.368車庫垂直電梯24386.000
10、.400.6034.4045.9057.369辦公生活水泵15757.000.700.8039.9029.9049.8610 消防水泵148.548.500.000.800.000.000.0011 辦公生活水轉(zhuǎn)輸泵14444.000.800.8035.2026.4044.0012 變配電房12020.000.900.8518.0011.2021.2013 弱電設(shè)施16060.000.900.8554.0033.5063.5514 防排煙設(shè)備(最大組合)1200200.000.000.800.000.000.0015 消控中心15050.000.800.8540.0024.8047.06四、空
11、調(diào)制冷設(shè)備16 水冷變制冷劑流量機組(主機)148.5119.000.900.80107.1080.30133.8617 水冷變制冷劑流量機組(主機)547.16386.640.900.80348.00261.00435.0018 水冷變制冷劑流量機組(主機)465.82267.720.900.80240.90180.70301.1419 水冷變制冷劑流量機組(主機)436.1262.300.900.80236.10177.10295.1420 冷卻水泵1115165.000.900.80148.50111.40185.6421 冷卻塔1115165.000.700.80115.5086.60
12、144.3622 新風(fēng)機組23060.000.800.8048.0036.0060.0023 排風(fēng)機組11111.000.800.808.806.6011.0024 低壓側(cè)合計4905.663344.802601.804237.5825 乘以同時系數(shù)0.903010.322341.623813.8226 自然功率因素cos0.7827 自動補償(kVar)(1152.00)28 總安裝補償容量(kVar)(1500.00)29 補償后0.933010.321189.623236.8530 變壓器容量(kVA)2x2000(kVA)4000.0031 變壓器負荷率0.8032 變壓器損耗32.3
13、7161.8433 變壓器高壓側(cè)計算負荷3042.691351.463329.32附表2.4 2#、3#樓辦公變配電房1,OT3、OT4負荷計算表序 用電設(shè)備組名稱數(shù)量/面積單位容量額定容量需用系數(shù)功率因數(shù)計算負荷號nkW/nkWKxCOSPjs(kW)Qjs(kvar)Sjs(kVA)一、商務(wù)辦公1辦公(包括空調(diào)負荷)292680.144097.520.700.852868.301777.603374.46二、公共設(shè)施2辦公公共區(qū)域64100.02128.200.700.8589.7055.60105.5335層架空層/航空障礙燈17280.0234.560.800.8527.6017.10
14、32.474預(yù)留泛光照明16060.000.500.8530.0018.6035.305預(yù)留廣告及LED屏照明16060.000.600.8536.0022.3042.356熱水器41560.000.200.8512.007.4014.10三、動力設(shè)備6垂直電梯1040400.000.400.60160.00213.30266.647變配電房12020.000.900.8518.0011.2021.208弱電設(shè)施16060.000.900.8554.0033.5063.559防排煙設(shè)備(最大組合)1200200.000.000.800.000.000.0010 消控中心15050.000.80
15、0.8040.0030.0050.0011 生活水泵162.562.500.800.8050.0037.5062.5012 低壓側(cè)合計5232.783385.602224.104050.7913 乘以同時系數(shù)0.903047.042001.693645.7114 自然功率因素cos0.8315 自動補償(kVar)(1001.00)16 總安裝補償容量(kVar)(1200.00)17 補償后0.953047.041000.693207.1518 變壓器容量(kVA)2x2000(kVA)4000.0019 變壓器負荷率0.8020 變壓器損耗32.07160.3621 變壓器高壓側(cè)計算負荷3
16、079.111161.053290.74附表2.5 商業(yè)變配電房1-3,RT1-RT8負荷計算表序 用電設(shè)備組名稱數(shù)量/面積單位容量額定容量需用系數(shù)功率因數(shù)計算負荷號nkW/nkWKxCOSPjs(kW)Qjs(kvar)Sjs(kVA)1地下二、三層非人防停車場794180.021588.360.700.851111.90689.101308.122B2設(shè)備房10000.0220.000.800.8516.009.9018.823商鋪259170.133369.210.700.852358.401461.602774.594餐飲135310.263518.060.700.802462.601
17、847.003078.285公共走廊(含中庭)340000.031020.000.700.85714.00442.50840.006設(shè)備房11500.0223.000.800.8518.4011.4021.657預(yù)留園林照明1100100.000.500.8550.0031.0058.838預(yù)留泛光照明1100100.000.500.8550.0031.0058.839預(yù)留廣告及LED屏照明1400400.000.700.85280.00173.50329.4010熱水器1300300.000.200.8560.0037.2070.6014垂直電梯1422308.000.400.60123.2
18、0164.30205.3615垂直電梯2714.000.400.605.607.509.3616垂直電梯31648.000.400.6019.2025.6032.0017自動扶梯4715705.000.700.80493.50370.10616.8618生活水泵1120120.000.700.8084.0063.00105.0019排水泵(最大組合)1300300.001.000.80300.00225.00375.0020裙樓防護冷卻供水設(shè)備15555.000.000.800.000.000.0021變配電房520100.000.900.8590.0055.80105.8922消防控制中心1
19、150150.000.900.85135.0083.70158.8423弱電機房1120120.000.900.85108.0066.90127.0424防排煙設(shè)備(最大組合)1300300.000.000.800.000.000.0025空調(diào)末端116001600.000.700.851120.00694.101317.6426AV設(shè)備1200200.000.800.85160.0099.20188.2628低壓側(cè)合計14458.639759.806589.4011775.9929乘以同時系數(shù)0.908783.825930.4610598.3930自然功率因素cos0.8231自動補償(kV
20、ar)(3044.00)32總安裝補償容量(kVar)(4320.00)33補償后0.958783.822886.469245.9334變壓器容量(kVA)2x2000+4x1600+2x800(kVA)12000.0035變壓器負荷率0.7736變壓器損耗92.46462.3037變壓器高壓側(cè)計算負荷8876.283348.769486.96附表2.6 商業(yè)變配電房4,RT9,RT10負荷計算表序 用電設(shè)備組名稱數(shù)量/面積單位容量額定容量需用系數(shù)功率因數(shù)計算負荷號nkW/nkWKxCOSPjs(kW)Qjs(kvar)Sjs(kVA)1SPA59000.251475.000.700.8510
21、32.50639.901214.712超市冷水機組1475475.000.800.80380.00285.00475.003超市冷卻水泵19090.000.800.8072.0054.0090.004超市冷凍水泵19090.000.800.8072.0054.0090.005超市冷卻塔12222.000.800.8017.6013.2022.006電影院冷水機組2201.5403.000.800.80322.40241.80403.007電影院冷凍水泵31133.000.800.8026.4019.8033.008商業(yè)冷卻水泵4200800.000.800.80640.00480.00800.
22、009商業(yè)冷凍水泵4200800.000.800.80640.00480.00800.0010商業(yè)冷卻塔918.5166.500.800.80133.2099.90166.5011低壓側(cè)合計4354.503336.102367.604090.8512乘以同時系數(shù)0.903002.492130.843681.7713自然功率因素cos0.8114自動補償(kVar)(1144.00)15總安裝補償容量(kVar)(1200.00)16補償后0.953002.49986.843160.5117變壓器容量(kVA)2x2000(kVA)4000.0018變壓器負荷率0.7919變壓器損耗31.611
23、58.0320變壓器高壓側(cè)計算負荷3034.101144.873242.91附表2.7 商業(yè)變配電房5,RT11,RT12負荷計算表序 用電設(shè)備組名稱數(shù)量/面積單位容量額定容量需用系數(shù)功率因數(shù)計算負荷號nkW/nkWKxCOSPjs(kW)Qjs(kvar)Sjs(kVA)1電影院47000.15705.000.700.85493.50305.80580.572地下二、三層人防區(qū)停車場400000.02800.000.700.85560.00347.10658.853地上停車場(B1)200000.02400.000.700.85280.00173.50329.404超市用電100000.12
24、1200.000.800.85960.00595.001129.445超市加壓、排煙1200200.000.000.850.000.000.006超市空調(diào)末端1200200.000.700.85140.0086.80164.727超市熱水器1100100.000.200.8520.0012.4023.538變配電房12020.000.900.8518.0011.2021.209弱電設(shè)施16060.000.900.8554.0033.5063.5510防排煙設(shè)備(最大組合)1200200.000.000.800.000.000.0011消防監(jiān)控中心15050.000.800.8040.0030.
25、0050.0012低壓側(cè)合計3935.002453.501520.602886.5013乘以同時系數(shù)0.902208.151368.542597.8514自然功率因素cos0.8515自動補償(kVar)(643.00)16總安裝補償容量(kVar)(960.00)17補償后0.952208.15725.542324.2918變壓器容量(kVA)2x1600(kVA)3200.0019變壓器負荷率0.7220變壓器損耗23.24116.2121變壓器高壓側(cè)計算負荷2231.39841.752384.88附表2.8 商業(yè)變配電房6,RT13,RT14負荷計算表序 用電設(shè)備組名稱數(shù)量/面積單位容量
26、額定容量需用系數(shù)功率因數(shù)計算負荷號nkW/nkWKxCOSPjs(kW)Qjs(kvar)Sjs(kVA)1百貨用電0.12160001920.000.800.851536.00951.901807.042加壓、排煙3001300.000.000.850.000.000.003變配電房20120.000.900.8518.0011.2021.204空調(diào)末端3001300.000.700.85210.00130.10247.035熱水器1001100.000.200.8520.0012.4023.536變配電房12020.000.900.8518.0011.2021.207弱電設(shè)施16060.0
27、00.900.8554.0033.5063.558低壓側(cè)合計2720.001856.001150.302183.569乘以同時系數(shù)0.901670.401035.271965.2010自然功率因素cos0.8511自動補償(kVar)(487.00)12總安裝補償容量(kVar)(750.00)13補償后0.951670.40548.271758.0814變壓器容量(kVA)2x1250(kVA)2500.0015變壓器負荷率0.7016變壓器損耗17.5887.9017變壓器高壓側(cè)計算負荷1687.98636.171803.88附表2.9 住宅變配電房1,T1,T2負荷計算表附表2.10 住
28、宅變配電房2,T3,T4負荷計算表序 用戶名稱住宅層數(shù)面積數(shù)量單位容量 負荷容量 需用系數(shù) 功率因數(shù)計算負荷序 用戶名稱住宅層數(shù)面積數(shù)量單位容量負荷容量需用系數(shù)功率因數(shù)計算負荷號(不計避難層)(m2)n(kW)kWKxCOSPjs(kW)Qjs(kvar)Sjs(kVA)號(不計避難層)(m2)n(kW)kWKxCOSPjs(kW)Qjs(kvar)Sjs(kVA)14棟(D型)住宅A戶530層251712511.6290.716棟(C型)住宅A戶532層271872712.7343.324棟(D型)住宅B戶530層262252615.3397.826棟(C型)住宅B戶532層28233281
29、5.8443.635棟(D型)住宅A戶530層251712511.6290.737棟(C型)住宅A戶532層271872712.7343.345棟(D型)住宅B戶530層262252615.3397.847棟(C型)住宅B戶532層282332815.8443.65住宅小計1377.00.600.80826.20619.701032.785住宅小計1573.90.600.80944.36708.301180.476消防電梯230.060.00.220.5513.2020.0023.966消防電梯230.060.00.220.5513.2020.0023.967非消防電梯430.0120.00.
30、220.5526.4040.1048.017非消防電梯430.0120.00.220.5526.4040.1048.018加壓風(fēng)機90.00.000.800.000.000.008加壓風(fēng)機90.00.000.800.000.000.009梯間照明210.020.00.700.8014.0010.5017.509梯間照明210.020.00.700.8014.0010.5017.5010低壓側(cè)合計1667.0879.80690.301118.2910低壓側(cè)合計1863.9997.96778.901265.9411乘以同時系數(shù)1.00879.80690.301118.2911乘以同時系數(shù)1.009
31、97.96778.901265.9412自然功率因素cos0.7812自然功率因素cos0.7813自動補償(kVar)(316.00)13自動補償(kVar)(354.00)14總安裝補償容量(kVar)(300.00)14總安裝補償容量(kVar)(300.00)15補償后0.92879.80374.30956.1115補償后0.92997.96424.901084.6516變壓器容量2x630(kVA)1260.0016變壓器容量2x800(kVA)1600.0017變壓器負荷率0.7517變壓器負荷率0.6718變壓器損耗9.5647.8118變壓器損耗10.8554.2319變壓器高
32、壓側(cè)計算負荷889.36422.11984.4519變壓器高壓側(cè)計算負荷1008.80479.131116.80附表2.11 住宅變配電房3,T5,T6負荷計算表附表2.12 住宅變配電房4,T7,T8負荷計算表序 用戶名稱住宅層數(shù)面積數(shù)量單位容量 負荷容量 需用系數(shù) 功率因數(shù)計算負荷序 用戶名稱住宅層數(shù)面積數(shù)量單位容量負荷容量需用系數(shù)功率因數(shù)計算負荷號(不計避難層)(m2)n(kW)kWKxCOSPjs(kW)Qjs(kvar)Sjs(kVA)號(不計避難層)(m2)n(kW)kWKxCOSPjs(kW)Qjs(kvar)Sjs(kVA)18棟(B型)住宅A戶533層282512817.14
33、77.919棟(A型)住宅A戶533層294182928.4824.328棟(B型)住宅B戶533層292512917.1495.029棟(A型)住宅B戶533層283782825.7719.73住宅小計972.90.600.80583.73437.80729.663住宅小計1544.00.600.80926.40694.801158.004消防電梯130.030.00.220.556.6010.0011.984消防電梯130.030.00.220.556.6010.0011.985非消防電梯230.060.00.220.5513.2020.0023.965非消防電梯230.060.00.22
34、0.5513.2020.0023.966加壓風(fēng)機45.00.000.800.000.000.006加壓風(fēng)機45.00.000.800.000.000.007梯間照明110.010.00.700.807.005.308.787梯間照明110.010.00.700.807.005.308.788生活水泵152.052.00.700.8036.4027.3045.508低壓側(cè)合計1689.0953.20730.101200.699低壓側(cè)合計1169.9646.93500.40817.879乘以同時系數(shù)1.00953.20730.101200.6910乘以同時系數(shù)1.00646.93500.40817
35、.8710自然功率因素cos0.7911自然功率因素cos0.7911自動補償(kVar)(325.00)12自動補償(kVar)(225.00)12總安裝補償容量(kVar)(378.00)13總安裝補償容量(kVar)(300.00)13補償后0.92953.20405.101035.7114補償后0.92646.93275.40703.1114變壓器容量2x630(kVA)1260.0015變壓器容量2x500(kVA)1000.0015變壓器負荷率0.8216變壓器負荷率0.7016變壓器損耗10.3651.7917變壓器損耗7.0335.1617變壓器高壓側(cè)計算負荷963.56456.891066.3918變壓器高壓側(cè)計算負荷653.96310.56723.95變壓器容量統(tǒng)計表技術(shù)經(jīng)濟指標(biāo)表裝設(shè)變壓器容量合計項目kVAkVA住宅2*500+4*630+2*8005120低層辦公(A、B座)2*20004000低區(qū)酒店和配套、后勤4*16006400中區(qū)和高層辦公2*20004000商業(yè)和地下室2*800+2*1250+6*1600+4*200021700商業(yè)10kV空調(diào)主機4*10504200共計45420